Modular electrical plug and plug-cable assembly including...

Electrical connectors – Contact comprising cutter – Insulation cutter

Reexamination Certificate

Rate now

  [ 0.00 ] – not rated yet Voters 0   Comments 0

Details

C439S676000

Reexamination Certificate

active

06193542

ABSTRACT:

FIELD OF THE INVENTION
This invention relates generally to electrical connectors and, more particularly, to multi-position modular plugs offering consistent near end crosstalk (“NEXT”) performance, i.e., NEXT values between wire pairs for plugs having the same design are substantially the same, and TOC (terminated open circuit) performance, i.e., TOC values between wire pairs for plugs having the same design are substantially the same. TOC performance relates to capacitive near-end crosstalk so that NEXT performance, which relates to both capacitive and inductive crosstalk, encompasses TOC performance.
The modular plugs in accordance with the invention may be used, depending on the construction, as Category 5, Category 5E or Category 6 plugs.
The present invention also relates to assemblies of the modular plug and a multi-wire cable terminated at one end by the plug and at the other end by another plug or another electrical connector.
BACKGROUND OF THE INVENTION
Data communication networks are being developed which enable the flow of information to ever greater numbers of users at ever higher transmission rates. However, data transmitted at high rates in multi-pair data communication cables have an increased susceptibility to crosstalk, which often adversely affects the processing of the transmitted data. Crosstalk occurs when signal energy inadvertently “crosses” from one signal pair to another. The point at which the signal crosses or couples from one set of wires to another may be 1) within the connector or internal circuitry of the transmitting station, referred to as “near-end” crosstalk, 2) within the connector or internal circuitry of the receiving station, referred to as “far-end crosstalk”, or 3) within the interconnecting cable.
Near-end crosstalk (“NEXT”) is especially troublesome in the case of telecommunication connectors of the type specified in sub-part F of FCC part 68.500, commonly referred to as modular connectors. The EIA/TIA (Electronic/Telecommunication Industry Association) of ANSI has promulgated electrical specifications for near-end crosstalk isolation in network connectors to ensure that the connectors themselves do not compromise the overall performance of the unshielded twisted pair (UTP) interconnect hardware typically used in LAN systems. The EIA/TIA Category 5 electrical specifications specify the minimum near-end crosstalk isolation for connectors used in 100 ohm unshielded twisted pair Ethernet type interconnects at speeds of up to 100 MHz.
A typical modular jack includes a housing having a cavity therein of a size for receiving a modular plug, where the cavity is provided with a plurality of cantilevered spring contacts which correspond to a like plurality of contact terminals in the mating modular plug. The modular plug receives discrete, insulated, stranded or solid conductors in conductor-receiving channels or slots formed in a dielectric housing. Flat, blade-like metallic terminals are then inserted into individual vertically oriented slots in the housing in a generally side-by-side arrangement with contact portions thereof extending into engagement with the conductors. When the plug is inserted into a modular jack, the cantilevered portions of the terminals in the jack engage portions of associated terminals in the plug.
The characteristics of Category 5 plugs must be verified to conform with FCC standard ANSI/TIA/EIA-568-A by measuring near-end crosstalk loss between the unshielded twisted pair conductor combinations when the plug is in an unmated state, i.e., when there is no current flow through the plug. This measurement is sometimes referred to as a “terminated open circuit” or TOC test.
In an eight-position modular plug, the contacts and twisted wires are numbered from
1
to
8
, from left to right with the contacts facing upward. Wires
4
and
5
form signal pair number
1
, i.e., they are operatively electrically coupled in an electrical circuit, wires
1
and
2
form signal pair number
2
, wires
3
and
6
form signal pair number
3
and wires
7
and
8
form signal pair number
4
. In this case, the TOC test is performed on the six different twisted pair conductor/wire combinations, namely the combinations of signal pair numbers 1 and 2, 1 and 3, 1 and 4,2 and 3,2 and 4, and 3 and 4.
To conduct the TOC test, the apparatus shown in
FIG. 1
is used. A 100 &OHgr; resistor
10
is connected in parallel with the 100 &OHgr; test leads
12
(where they connect to the wideband baluns 14) and NEXT is measured by the network analyzer
16
. The measured NEXT loss at 100 MHz must be in the range shown in Table 1.
TABLE 1
Wire Pair Combination
Test Plug NEXT loss at 100 MHz
1 and 2
≧55 dB
1 and 3
≧40 dB
1 and 4
≧55 dB
2 and 3
≧45 dB
2 and 4
≧55 dB
3 and 4
≧45 dB
In addition, for wire pair combination 1 and 3, the difference between the NEXT loss measured at 100 MHz and the NEXT loss measured at 10 MHz must be 20 ±0.5 dB. Additional TOC requirements for wire pair combination 1 and 3 of the test plugs include: at least one of the test plugs must exhibit NEXT loss in the range of ≧ 40.0 dB to <40.5 dB at 100 MHz; at least one of the test plugs must exhibit NEXT loss in the range of ≳ 40.5 dB to <41.5 dB at 100 MHz; and at least one of the test plugs must exhibit NEXT loss in the range of ≧ 41.5 dB at 100 MHz;
Conventional modular plugs include one or more load bars for receiving the conductors in separate conductor-receiving passages. The use of load bars contributes to control of the inter-conductor capacitance in the plug.
FIG. 2
shows typical TOC values measured for ten eight-position modular plugs of the same design between the pair combination 2 and 4, specifically, an RJ45 plug having two load bars terminating a 24 AWG Tinned Stranded UTP cable made by Lucent Technologies. As shown in
FIG. 2
, for eight-position modular plugs having the same design, TOC values can vary by as much as 40 dB between plugs (compare test plugs 1 and 10). This variation is partially due to the relatively random arrangement of the unshielded twisted pairs (UTP) of conductors in the body of the plug, i.e., in the wire-receiving channels in the plug body, which causes small changes in the capacitance between the conductors.
One way to reduce inter-conductor capacitance in a plug is by offsetting adjacent conductors. Examples of this type of plug are disclosed in U.S. Pat. No. 5,628,647 (Rohrbaugh et al.) wherein the conductors are arranged in two planar arrays spaced one above the other. The offset conductors helps lower the plug's internal capacitance but does not result in stable TOC values for plugs having the same design.
In another attempt to stabilize the capacitance in an RJ45 plug in order to obtain consistent TOC values for plugs having the same design, three plugs
20
were assembled with four load bars
22
each (FIG.
3
). The plugs initially were a standard RJ45 plug manufactured by Stewart Connector Systems but modified to include four load bars, and as tested, terminate a Berk-Tek Lan-Mark-350 cable (the same cable is used in all of the TOC tests described herein unless stated to the contrary). The use of four load bars fixed the inter-conductor capacitance within the length of the body of the plug. TOC measurements were then made on each pair combination to determine the degree of TOC stability. As shown in
FIG. 4
, the TOC values measured on the three plugs using four load bars each had less than a 4 dB variation from plug to plug.
Although the measured TOC values for a four-load bar plug as shown in
FIG. 4
exhibits less variation from plug to plug than a standard Category 5, eight-position modular plug using two load bars, the wire pair combination 1 and 3 does not always yield a TOC value that complies with the requirements of TIA/EIA-568A. Indeed, the lowest TOC value obtained in the three plugs tested is 39.8 dB between the wire pair combination 1 and 3. However, the minimum requirement for pair combination 1 and 3 is 40 dB (See Table 1) and thus these modified plugs would not pass t

LandOfFree

Say what you really think

Search LandOfFree.com for the USA inventors and patents. Rate them and share your experience with other people.

Rating

Modular electrical plug and plug-cable assembly including... does not yet have a rating. At this time, there are no reviews or comments for this patent.

If you have personal experience with Modular electrical plug and plug-cable assembly including..., we encourage you to share that experience with our LandOfFree.com community. Your opinion is very important and Modular electrical plug and plug-cable assembly including... will most certainly appreciate the feedback.

Rate now

     

Profile ID: LFUS-PAI-O-2613476

  Search
All data on this website is collected from public sources. Our data reflects the most accurate information available at the time of publication.