Liquid heaters and vaporizers – Steam treatment – Automatic heat regulation of superheater
Reexamination Certificate
2002-02-27
2003-08-26
Wilson, Gregory (Department: 3749)
Liquid heaters and vaporizers
Steam treatment
Automatic heat regulation of superheater
C122S166200
Reexamination Certificate
active
06609483
ABSTRACT:
FIELD AND BACKGROUND OF THE INVENTION
The present invention is generally drawn to broilers using SCR (Selective Catalytic Reduction) systems at the flue exhaust to clean the exhaust gas thereby and more particularly to the optimized temperature operation of the same.
In operating a boiler with a Selective Catalytic Reduction system, or SCR, at the flue gas exhaust, the reactiveness of the catalyst is dependent upon the flue gas temperature entering the catalyst reactor. A given catalyst will have maximum performance when it is operated at the temperature of peak performance (TPP). As an example, in a typical SCR for NO
x
removal, the temperature of peak performance (typically 650° F.) at the reaction of ammonia with NO
x
present in the flue gas is optimized and the amount of the ammonia needed for the catalytic reaction is minimized. Therefore, for economic reasons the desired gas temperature entering the catalyst reactor should be maintained at the TPP at all loads. Also, maintaining the desired flue gas temperature reduces the formation of ammonia and/or sulfate salts within the ammonia injection grid (AIG) and the catalyst.
However, as boiler load decreases, the boiler exit gas temperature will drop below the TPP. To increase the gas temperature to TPP, current practice has been to use an economizer gas bypass. The economizer gas bypass is used to bypass the hotter gases upstream of the economizer to the cooler gas that leaves the economizer and mixes with the flue gas. By controlling the amount of gas that passes through the bypass system, a boiler exit flue gas temperature of approaching the TPP can be maintained at the lower boiler loads which normally results in the flue gas temperature below TPP.
Also, systems for mixing economizer feedwater with hot water at the inlet of the economizer are known. These systems were known as the Off Line Circulation System and were developed in the mid 1980s. However, this system was not designed for increasing the flue gas temperature from the economizer. This system's main purpose was to reduce the economizer inlet headers thermal shock that occurs during boiler start up and shut down and to eliminate the stratification/subcooling temperature effects that occur in the furnace walls of the boiler when the boiler is off line and put into hot standby.
Thus, what was needed was a simpler system that required less physical space to obtain the desired flue gas temperature to the SCR at various boiler loads. With the known flue gas bypass systems currently used for SCR application, static mixing devices, pressure reducing vanes/plates and thermal mixing devices were required to make the different temperature flue gases mix before the gas mixture reaches the inlet of the catalyst reactor. In most applications, obtaining the strict mixing requirements for flow, temperature and the mixing of the reagent (if received) before the catalyst reactor was often difficult.
SUMMARY OF THE INVENTION
The present invention solves the problems associated with prior art devices as well as others by providing a boiler water recirculation system where the variation in the gas flow and temperature at the economizer outlet is less severe than with a flue gas bypass system, making it easier to meet the gas mixing requirement for the catalyst reactor at the optimal inlet temperature.
To accomplish this, the invention uses the economizer to increase the outlet temperature of the flue gases to the desired temperature at the lower boiler loads by using a boiler recirculation system to provide higher temperature water from the circulation system that is used to cool the furnace walls. The recirculation system supplies near saturation water from the downcomers of drum circulation boiler applications, or for once-through boiler applications, the fluid is obtained from a fluid mix location in the upper region of the lower furnace. In either a drum or once through boiler application, the higher temperature water is transferred to the economizer inlet and mixed with the boiler's economizer normal feedwater inlet flow. The mixture of the two fluid streams results in a higher temperature fluid in the economizer that can be used to increase the flue gas temperature leaving the economizer. With proper adjustment of the different fluid streams to the economizer, the desired flue gas temperature can be obtained for any boiler load. The amount of near saturation water (or higher temperature furnace wall water for a once-through boiler) from the boiler recirculation system is controlled throughout the load range. Calculations have shown that no catastrophic effects (critical heat flux or tube failures) on the cooling of the boiler's furnace walls will occur in the use of this system.
In view of the foregoing it is seen that one aspect of the present invention is to provide stable flue gas temperature control system based on economizer water inlet temperature.
Yet another aspect of the present invention is to provide an increased temperature economizer gas outlet responsive to increased economizer water inlet temperature.
These and other aspects of the present invention will be more fully understood upon a review of the following description of the preferred embodiment when considered in conjunction with the accompanying drawings.
REFERENCES:
patent: 4887431 (1989-12-01), Peet
patent: 5555849 (1996-09-01), Wiechard et al.
patent: 5603909 (1997-02-01), Varner et al.
patent: 5713311 (1998-02-01), Fitzgerald
patent: 5943865 (1999-08-01), Cohen
patent: 5988115 (1999-11-01), Anderson et al.
patent: 6510820 (2003-01-01), McDonald
Albrecht Melvin J.
Rogan John B.
Grant Kathryn W.
Marich Eric
The Babcock & Wilcox Company
LandOfFree
System for controlling flue gas exit temperature for optimal... does not yet have a rating. At this time, there are no reviews or comments for this patent.
If you have personal experience with System for controlling flue gas exit temperature for optimal..., we encourage you to share that experience with our LandOfFree.com community. Your opinion is very important and System for controlling flue gas exit temperature for optimal... will most certainly appreciate the feedback.
Profile ID: LFUS-PAI-O-3093165