Motorized insulated damper assembly for furnace systems

Stoves and furnaces – Dampers – Electric

Reexamination Certificate

Rate now

  [ 0.00 ] – not rated yet Voters 0   Comments 0

Details

C126S28500B, C126S112000, C126S08500R, C454S333000, C236S00100H

Reexamination Certificate

active

06213117

ABSTRACT:

BACKGROUND OF THE INVENTION
The present invention relates in general to furnace dampers, and more specifically, to furnace dampers which can selectively provide fresh air to a furnace while the furnace is in operation, and which can be effectively sealed when the furnace is not in operation.
Newer technologies in home construction have resulted in homes which are more and more “air tight.” As a result, these homes are more completely closed and do not allow fresh air to flow into the structure. However, research has shown that a certain amount of fresh air flow is needed to dilute man-made household pollutants which may exist in a home, such as formaldehyde found in paints, volatile organic compounds found in sealants, and toluene found in binders. In order to combat these pollutants, efforts have been made in the area of furnace filter designs to improve the quality of indoor air. However, due to maintenance problems and certain design limitations, these furnace filters do not adequately remove harmful pollutants.
In general, when fresh air flow is increased, the indoor air quality is also increased. At least in part due to these concerns regarding the introduction of fresh air into modern homes, changes were made in the 1991 Uniform Mechanical Code (UMC) provisions regarding fresh air introduction for furnaces with respect to air supply. The UMC now requires that a fresh air intake of 15 cubic feet per minute (cfm) per person be supplied by an outside source. Section 706 of the UMC states:
Circulating air shall be taken from outside the building or from the conditioned space, or both. Heating systems regulated by this code and designed to replace required ventilation shall be arranged to discharge into the conditioned space not less than the amount of outside air specified in the Building Code.
A typical ventilation standard which is used by many engineers is the American Society of Heating, Refrigeration, and Air-Conditioning Engineers Standard 62-1989. This standard recommends 0.35 air changes per hour, but not less than 15 cfm per person fresh air flow.
Attempts have been made to meet this standard by providing a “passive” fresh air system. This passive fresh air system utilizes an air duct that connects an outside air source to the return air duct of the furnace system via a fresh air supply duct. In this passive fresh air system, fresh air is drawn into the return air duct simply from the suction generated by the main blower fan of the furnace. Thus, these passive systems have been designed to rely upon the main blower fan of the furnace to provide the required amount of suction so that a minimum of 15 cfm per person of fresh air is drawn into the return air duct of the furnace system. This passive system does not regulate the amount of fresh air actually entering the system and does not ensure that the standard of 15 cfm per person of fresh air is being met.
Along with the above disadvantages, the passive fresh air systems being used do not prevent fresh air from flowing into the return air duct of the furnace when the main blower fan of the furnace is not operating. Thus, unwanted outside air can enter the return air duct of the furnace system even when the main blower fan of the furnace is not in operation. Unwanted cold air increases the amount of heating the furnace must accomplish, which in turn increases the overall energy costs to the consumer. Further, the entrance of cold air into the return air duct in extremely cold environments can result in damage to pipes which may exist in and around the furnace.
Additional problems also exist when excess cold air enters the return air duct of the furnace system. The cold air may cause the products of combustion (principally carbon monoxide, carbon dioxide and water vapor) to condense on the inner surface of the heat exchanger. This condition creates an environment in which the combustion gasses begin to condense out and cause the formation of carbonic acid. This carbonic acid may damage the interior of the furnace through corrosion, causing a reduction in the useful life of the furnace. If a sufficient amount of corrosion takes place, a health hazard may exist if cracks form in the heat exchanger. The existence of cracks in the heat exchanger can cause the heating chamber to fracture which may allow carbon monoxide to mix with the heated air in the room, or to be exhausted improperly. As is well known, carbon monoxide poisoning can lead to illness and sometimes death.
Therefore, an electrically controlled damper is needed which can inject the proper volume of fresh air into the return air duct of a furnace system. Further, an electrically controlled damper is needed which will substantially prevent unwanted fresh air from entering the return air duct when the furnace is not in operation.
SUMMARY OF THE INVENTION
It is therefore an object of the present invention to provide an electrically controlled damper which operates to inject the proper volume of fresh air into the return air duct of a furnace system when the furnace is in operation.
It is a further object of the invention to provide an electrically controlled damper which will substantially prevent unwanted fresh air from entering the return air duct of the furnace system when the furnace is not in operation.
It is another object of the invention to provide a damper which allows communication between a fresh air source and a furnace system and which can be effectively insulated from the fresh air source when the damper is in a closed position.
According to one aspect of the present invention, the foregoing and other objects are achieved by a damper unit adapted to be positioned in a furnace duct line. The damper unit has a housing which is in communication with a fresh air source and a furnace system. The housing has a damper blade which is moveable between an open position which allows air flow through the housing and a closed position which prevents air flow through the housing. The blade is coupled with a solenoid so that when the solenoid is activated the blade is moved to an open position allowing air flow through the housing. Further, a fan is located in the housing adjacent the damper blade. The fan operates to move air into and out of the housing and across the damper blade when the damper blade is in its open position.
In another aspect of the invention, a pair of sealing ridges are provided on the interior of the housing. When the damper blade is in a closed position, it is in abutting relationship with the sealing ridges so that air flow across the closed damper blade is substantially prevented by the damper blade and the sealing ridges.
Additional objects, advantages, and novel features of the invention will be set forth in part in the description which follows, and in part will become apparent to those skilled in the art upon examination of the following, or may be learned from practice of the invention. The objects and advantages of the invention may be realized and attained by means of the instrumentalities and combinations particularly pointed out in the appended claims.


REFERENCES:
patent: 1767869 (1930-06-01), Baumgarten
patent: 1828016 (1931-10-01), Andres
patent: 1879342 (1932-09-01), Lauter
patent: 2039948 (1936-05-01), Best
patent: 2224705 (1940-12-01), Stringer
patent: 2467018 (1949-04-01), Eggleston
patent: 2579395 (1951-12-01), Pfautsch
patent: 2800853 (1957-07-01), Spear
patent: 2856484 (1958-10-01), Fairbanks
patent: 2962218 (1960-11-01), Dibert
patent: 3004484 (1961-10-01), Lorenz
patent: 3821924 (1974-07-01), Walters
patent: 3964377 (1976-06-01), Chapman
patent: 4121562 (1978-10-01), Grott
patent: 4122835 (1978-10-01), Bowen, Jr. et al.
patent: 4141336 (1979-02-01), Fitch
patent: 4193541 (1980-03-01), Scheildweiler
patent: 4206744 (1980-06-01), Mahoney et al.
patent: 4249883 (1981-02-01), Woolfolk
patent: 4292950 (1981-10-01), Schossow
patent: 4372196 (1983-02-01), Henderson
patent: 4537117 (1985-08-01), Cvaestany et al.
patent: 4777928 (1988-10-01), Ellis
patent: 4920866 (1990-05-01), Hoban
patent: 5012793 (1991-05-01), Guzorek
pat

LandOfFree

Say what you really think

Search LandOfFree.com for the USA inventors and patents. Rate them and share your experience with other people.

Rating

Motorized insulated damper assembly for furnace systems does not yet have a rating. At this time, there are no reviews or comments for this patent.

If you have personal experience with Motorized insulated damper assembly for furnace systems, we encourage you to share that experience with our LandOfFree.com community. Your opinion is very important and Motorized insulated damper assembly for furnace systems will most certainly appreciate the feedback.

Rate now

     

Profile ID: LFUS-PAI-O-2521928

  Search
All data on this website is collected from public sources. Our data reflects the most accurate information available at the time of publication.