Fault location device and method

Electricity: measuring and testing – Fault detecting in electric circuits and of electric components – For fault location

Reexamination Certificate

Rate now

  [ 0.00 ] – not rated yet Voters 0   Comments 0

Details

C324S539000

Reexamination Certificate

active

06819115

ABSTRACT:

BACKGROUND OF THE INVENTION
This invention relates to a fault location device and method, useful for determining the position of a fault in a cable.
Buried underground cables and pipes (often referred to as “services”) sometimes develop faults and are not always clearly marked on plans, especially if they were not recently installed.
Precise fault location is desirable in the interests of reducing the amount of digging required to repair the cable. Underground cables can develop a number of different faults. Some examples are:
open circuit;
short circuit to another conductor;
short circuit to the shield; and
short circuit to the ground, also known as a sheath fault because the cable sheath has been breached.
A fault of primary interest is the sheath fault. One common method of detecting the location of this is to use a ground probe to search for maximum signal strength. This is effective because the ground is a volume conductor and the fault current is denser near the fault than it is as one moves further away. The maximum current point will be nearest the fault. One drawback of this method is that it is not possible to tell the direction to the fault and one must hunt to find whether one is moving closer to the fault or further from it. It is possible to address this limitation by various methods.
One method employs a large DC voltage to produce a deflection on a DC voltmeter. The direction of the deflection shows the direction to the fault, as the current flow is always away from the fault. The disadvantages of this method are that there are often DC current offsets in the soil which can give false readings and most cable connected equipment may not be tolerant of high DC voltage levels.
Another method is to use a very large voltage pulse to produce a deflection on a meter. The direction of the deflection shows the direction to the fault. The disadvantages if this method are that it is unreliable in wet soil, and the voltage pulse can damage the cable insulation or connected devices. The advantage over the DC voltage method is that it reduces problems due to local DC or very low frequency AC currents in the soil.
A further method involves adding a higher frequency carrier signal which is picked up by an antenna. This is processed and compared to the signal in the ground to determine the polarity of the signal in the ground. This method has the advantage that the ground signal can be a continuous AC signal. The drawback is that one must keep the receiving device locked to the cable frequency, and higher frequencies have a lower range.
Another method uses multiple harmonically related frequencies simultaneously to try and calculate the direction to the fault. The phase relationships of the signals are compared and the sign of the deviation between them is used to determine the direction to the fault. The sign of the phase deviation is equal to the polarity of the signal and hence the direction can be calculated. The advantages of this method are that it lessens the problems with DC signals, and also overcomes the need to keep the receiver locked to an external signal on the cable. The disadvantage is that errors in signal phase caused by noise and mains switching transients can produce incorrect results, effectively pointing the user of the device in the wrong direction.
A method of sheath fault location using a transmitter and a ground probe based receiver illustrated in FIG.
1
.
A signal is placed on the cable
14
at a convenient access point by use of a generator
20
. The return path for the signal is ground. The actual conductor used is the one with the sheath fault on it, otherwise there would be no return current. The fault is represented by an impedance
22
to ground and located at location
23
along the cable. In practice, the ground return path is complex and depends on the type of soil, moisture content, depth of cable and the presence of other buried conductors such as metal water pipes.
A ground probe
24
, represented as a volt meter, is used to measure the voltage potential in the ground to determine the direction from the ground probe to the fault. This has two ground probe elements
24
a
,
24
b
which are positioned in spaced relationship in the ground, the probe if necessary being moved to various successive ground locations at which the probes are entered into the ground, and meter readings taken at the voltmeter.
Near to the fault, the ground currents branch out from the fault. Because of this, the ground probe can correctly identify the direction to the fault from either side of the fault. Directly over the fault, there is no signal at all and it is by determining the location of the probe at which this result ensues that the location
23
of the fault is determined. This is illustrated in
FIG. 2
where the currents branching out from cable
14
at the fault are illustrated diagrammatically by arrows
26
, and the polarities of detected signal at the voltmeter when positioned along the length of the cable, but to opposite sides of the fault is shown as being relatively reversed. There is no detected signal when the voltmeter is positioned adjacent the fault, and this is how the fault is located.
To reduce losses due to cable capacitance, lower frequencies are preferred. But frequencies in the normal operating range of the cable may cause cross talk and interference to other cables. As a result, frequencies below 300 Hz or above 3.4 KHz may be preferred. Frequencies below 300 Hz are however close to the harmonics and fundamentals of power frequency transmission equipment. As a result, signals well below 50/60 Hz may be most preferable.
There are three basic methods that might be used to show the direction to fault:
DC shift;
cable carrier and/or locked carrier reference; and
phase deviation.
The DC shift method involves either placing a large DC voltage on the cable or using a large pseudo impulse. The latter is preferable because it is less susceptible to local DC and low frequency AC currents, but both methods suffer from limited range in the wet and the possibility of damaging the cable.
The method cable carrier and/or locked carrier reference involves locking an on-board reference to the transmitter. This can be most easily achieved by sending a carrier signal down the same cable and picking it up with an antenna. Alternatively, a radio based carrier system could be used. Another method is to lock the receiver to the transmitter and hold the lock using a very low drift oscillator. In practice, a low drift oscillator locked to a cable borne signal may be more easily achieved. The disadvantage is that cable borne signal must be a high enough frequency to be readily picked up by a compact antenna and this normally brings it into or above the voice band. Signals in the voice band are not preferred by telecommunications carriers and higher frequencies are harder to keep phase aligned due to capacitive effects in the cable.
The phase deviation method involves using more than one frequency and measuring the direction of phase deviation between the two signals. If the direction of deviation is one polarity, then the fault lies in one direction, otherwise it lies in the other. These methods suffer from the fact that phase distortion or noise can cause erroneous results, even reversing the direction. Lower frequencies are preferred to improve range and reduce phase distortion due to capacitive effects, but because of the close proximity to mains power frequencies and their harmonics, substantial filtering is required. Filters are difficult to make phase shift free, and high Q band pass filters can ring in the presence of noise and switching transients, giving rise to false detections and incorrect direction results. At the very least, careful phase alignment is required.
In all of the above cases, it is difficult to provide high confidence that the user will correctly interpret the results and know when to ignore spurious readings.
The DC shift method involving high voltage pseudo impulses requires the operator to ignore slowly drifting meter movements, an

LandOfFree

Say what you really think

Search LandOfFree.com for the USA inventors and patents. Rate them and share your experience with other people.

Rating

Fault location device and method does not yet have a rating. At this time, there are no reviews or comments for this patent.

If you have personal experience with Fault location device and method, we encourage you to share that experience with our LandOfFree.com community. Your opinion is very important and Fault location device and method will most certainly appreciate the feedback.

Rate now

     

Profile ID: LFUS-PAI-O-3342415

  Search
All data on this website is collected from public sources. Our data reflects the most accurate information available at the time of publication.