Reduction of harmonics in AC machines

Electricity: electrical systems and devices – Safety and protection of systems and devices – With tuned circuit

Reexamination Certificate

Rate now

  [ 0.00 ] – not rated yet Voters 0   Comments 0

Details

C307S105000, C174S018000

Reexamination Certificate

active

06577487

ABSTRACT:

TECHNICAL FIELD
A voltage of a frequency three times the frequency of the network, referred to below as the third harmonic, is generated in different ways in distribution and transmission networks, commonly referred to below as power networks. This voltage generates a third-harmonic current which often causes great problems, on the one hand for apparatus and attachments connected to the power network, and on the other hand for the third-harmonic generating devices themselves. The third-harmonic problems are often directly associated with the way the connected devices are grounded. Because there are several different principles and regulations for grounding in power networks it follows that the methods for reducing influence from third harmonics can be extremely different. The present invention deals with how to reduce the problems with third-harmonic currents that may arise during generator and motor operation of AC machines. The invention consists of a method and a connection arrangement for achieving the above mentioned.
BACKGROUND ART, THE PROBLEM
When calculating and designing three-phase AC machines, the aim is normally to achieve as symmetrical and sinusoidal quantities as possible. With respect to terminals the stator windings of the above-mentioned machines may, when being manufactured, be connected in many different ways. For some machines the stator windings are connected in &Dgr;, for others in Y-connection, where the so-called neutral point sometimes is not drawn out from the machine. For the machines concerned in this invention the three-phase winding is Y-connected and all of the winding ends including the neutral point are drawn out from the machine. In order to obtain an economic yield from the electromagnetic circuit in common types of AC machines, a third-harmonic EMF is generated as a harmonic to the fundamental EMF.
It is well known that the chording of the stator winding may be chosen in order to eliminate one or more of the harmonics. It is also well known regarding synchronous AC machines with salient poles that, in addition, the shape of the EMF of these machines may be influenced and improved by choosing the design of the rotor poles and, especially, the shape of the pole shoes in an appropriate way.
A total elimination of the third harmonic of the voltage by choosing an appropriate size for the winding step however means a considerable reduction, approximately
14
%, of the fundamental frequency voltage available for torque generation. This thus means only 86% utilization of the possible rated power. In order to avoid this reduction, the winding step is used mainly for suppression of the fifth harmonic whereby the reduction becomes only a few percent. Adaptation of the shape of the pole shoe is often used for a cost-effective reduction of the seventh harmonic voltage. Elimination or reduction of the harmful effects of the third-harmonic voltage/current must thus be performed by different methods.
When a generator is to be connected directly to an existing power network the grounding of the generator cannot normally be freely chosen due to the fact that this is mainly determined by the grounding method of the existing power network. Concerning grounding, however, there are important criteria which should be fulfilled, namely:
the power network may be directly grounded, resonance-grounded, ungrounded, high-impedance grounded
a third-harmonic current through the generator as well as other equipment connected in the power network must for many reasons be limited
If the neutral point is connected to the ground of the power network by a relatively high-ohmic impedance for both the fundamental and the third component, increased voltages relative to ground will arise on the unfaulted phases in case of a ground fault. This cannot be accepted on certain markets.
By connecting the neutral point directly, or via an appropriate impedance, to the ground of the power network, this will however allow the AC machine concerned to contribute to obtain appropriate magnitudes of the zero-sequence impedances to be able to handle the fault conditions, for example voltage increases on unfaulted phases, which may arise in the electrical system.
Traditionally, certain criteria should be fulfilled concerning the zero-sequence impedance R
0
+jX
0
and positive-sequence reactance X
+
of the systems. These criteria are often denoted as the following inequalities and state that
X
0
/X
+
<3 and R
0
/X
+
<1
In other respects, these inequalities can be interpreted in such a way that in case of a ground fault in one phase, the voltage increase, in the unfaulted phases relative to ground, can be limited to 80%, which is an economical value from the point of view of insulation coordination, of what would have occurred if X
0
and/or R
0
→∞.
The disadvantage with a direct connection of the neutral point to the ground of the power network is that, if the voltages contain a third harmonic, a third-harmonic current will start to flow in the phase conductors which closes its circuit through the ground and/or the neutral conductors. It can be mentioned that there are no regulations prohibiting such an arrangement and that there are such installations in operation.
Concerning low-voltage power networks, there are today in most networks third-harmonic currents which close their circuit through the neutral conductor and cause thermal as well as acoustic problems. The occurrence of and a method of reducing the influence of these third-harmonic currents will be described below.
When it comes to limiting the detrimental effect of the third-harmonic voltage and the third-harmonic current, there are a number of different methods in addition to grounding of the neutral point by means of appropriate impedances.
A relatively common method of grounding is to connect a high-ohmic resistance to a point on the power network which is always connected. This can be done by means of a Z/0-connected transformer connected to the network. To obtain the required selective ground fault protection devices, however, the resistance should be dimensioned such that at least, a ground fault current at full neutral point voltage is obtained.
Another common method for handling the third-harmonic problems for generator plants where the neutral point is available and which, in addition has obvious advantages with regard to limiting fault current in case of a ground fault in the generator appears from the accompanying
FIG. 1. A
generator
1
has the neutral point
2
via an impedance
3
, low ohmic resistor often a neutral-point resistor dimensioned for ground fault current of some harmless 10-20 amperes or so, connected to the ground of the power network
4
. A ground fault in the generator thus can cause a ground-fault current via the impedance, and by controlling the ground fault current, measures can be taken to disconnect the generator or a possible defective phase. The phase voltages of the generator are connected to a &Dgr;/Y−0 connected so-called step-up transformer
3
which has to be dimensioned for full power even if it should not be reason to change the voltage level. A ground fault in the A-winding of the transformer is limited, in the same way as for a ground fault in the windings of the generator, to some 10-20 amperes. The third-harmonic voltages with which the generator is afflicted could give a third-harmonic current. However, the third-harmonic voltage is superimposed on the phase voltages of the E-winding but cannot generate any third-harmonic current via the neutral-point resistance to ground. This means that, on the Y-side of the transformer, i.e. on the power network side, no third-harmonic current is sensed. In
FIG. 1
the necessary auxiliary power input from the network and the field excitation of the generator are omitted. As is otherwise clear from the figure, current measurement devices
6
and
7
are needed for the ground fault current and for the current delivered from the generator. On the generator side, in addition, both a disconnector and a circu

LandOfFree

Say what you really think

Search LandOfFree.com for the USA inventors and patents. Rate them and share your experience with other people.

Rating

Reduction of harmonics in AC machines does not yet have a rating. At this time, there are no reviews or comments for this patent.

If you have personal experience with Reduction of harmonics in AC machines, we encourage you to share that experience with our LandOfFree.com community. Your opinion is very important and Reduction of harmonics in AC machines will most certainly appreciate the feedback.

Rate now

     

Profile ID: LFUS-PAI-O-3150018

  Search
All data on this website is collected from public sources. Our data reflects the most accurate information available at the time of publication.